            YB 24KV(15)KV intelligent/compact box-type substation

            Compact box-type substation of 24kV(15kV) (hereinafter referred to as box-type substation) takes the advantages of foreign box-type substations, employs the new techniques, advanced electric parts and HV/LV automated technology, it meets the requirements of the state grid automation and electric power requirements. It is formed a box or several boxes that are assembled with HV switchgear, distribution transformer, LV switchgear, electric energy metering equipment and power compensation equipment. The intelligent module is installed on its HV and LV side, to reach the requirements of automation in the distribution grid and realize the remote control, remote sensing, remote signaling and remote regulating as well as upper computer system management. This equipment is applicable for the locations such as the urban high-rise buildings, residential houses, industrial and mining enterprises, municipal constructions, roads and street lamps as well as the temporary constructions.It has many advantages such as the strong completeness, short installation period, small floor area, low investment, less maintenance, reliable operation, nice appearance, long service life, in addition, it is easy to harmonize with the surroundings.

            Read More>>


            Product Detail

            Product Tags

            Model and meaning

            dcbe1c623

            Use environmental conditions

            Normal service conditions of outdoor box-type substation
            a) The ambient temperature shall not exceed +40℃,and the average temperature within 24h shall not be more than +35℃ .The min ambient temperature may be -10 degree 5 and -25℃ . What’s more, the sharp change of temperature shall be taken into consideration.
            b)The sunshine radiation of3,000W/㎡ (Atnoon on acloudless day shall be taken into consideration.
            c) The altitude shall not be higher than 1,000m.
            d) If the ambient air is subject to the pollution of dust, smoke, corrosive gas, steam or salt mist, the pollution class shall not exceed the class Ⅲ .
            e) For class 1, the ice coating thickness shall not exceed 1mm; for class 10, it shall not be thicker than 10mm; and for class 20; it shall not be more than 20mm.
            f) The wind speed shall not exceed 34m/s.
            g) The condensation and precipitation shall be taken into consideration.
            h)The inductive electromagnetic disturbance voltage range shall not be more than 1.6kV in the secondary system . Special service conditions If beyond the normal service conditions mentioned in clause 3.1, please contact and negotiate with the manufacturer.

            The main technical parameters

            Rated voltage (Ur): On the HV side: 24kV/15kv On the LV side: 0.4kV
            Auxiliary circuit: AC110V, 220V and 380V; DC 24V, 110V, 125V
            Rated capacity of transformer: 100, 125, 160, 200, 250, 315, 400, 500, 630, 800, 1,000, 1,250, 1 ,600kVA
            Rated current (Ir): On the HV side: 400A and 630A On the LV side: Max 2,500A
            Rated frequency (fr): 50Hz
            Rated short-time withstand current (Ik) :
            HV switchgear: 16kA 2s(4s), 20kA 2s(4s)
            LV switchgear: 15kA for 315~500kVA 30kA for 630~1,600kVA
            Test time: 1s If the capacity of transformer is less than 315kVA, the equipment will be exempted from the test.
            International protection of enclosure : Not lower than IP23D

            Structural features

            1. This design considers the territory, environment and variety of customer demands, it employs the modular structure combined with following types. According to the HV switch connecting with the power grid: ring net type, terminal type, HV energy metering type, LV energy metering type. According to the equipment arrangement: Chinese character"..” type structure and Chinese“ ..”type structure.
            According to the type of built-in transformer: oil- immersed full- seal transformer and dry- type transformer. According to the type of HV switch: vacuum type load switch and combination unit switch gear, SF6 load switch and combination unit switch, gas-filled switchgear According to the material of box body (enclosure) : metallic enclosure and non- metallic enclosure The metallic enclosure and frame are welded with the beam channel and steel I beam, the side wall and top cover is of two-layer assembly, the outer has the hoisting pin and mounting pin, the metallic door has the good earthing line and the under frame and foundation has the connecting earthling conductor. There are doors installed on both sides of transformer, which facilitate the installation and repair of the transformer; and safe and isolating net doors to prevent person entering into electrical isolating area by mistake and guarantee the safety of equipment and human.
            2. Good ventilation measures: the structure of box body is of two layers, the top of box is else made of heat - isolation material, which can lower the rise of indoor temperature caused by the sunshine and there is an automatic ventilator mounted at the side door of HV chamber, which can ensure transformer run safely in full load in the high temperature season.
            3. The HV switchgear on HV side provided with five-prevention measures and there is an energized reliable lock with the transformer compartment to ensure the human security. The Protection degree of box body can reach IP23D: It has good rain-proof performance.
            4. Convenient operation and maintenance There are some visible marks outside of the box type substation , indicating the HV compartment, through opening the compartment doors, they can be easily operated and repaired,each compartment has the automatic lighting device even the compartment of transformer is used for installing . maintaining and changing the transformer in addition LV compartment is of force connection and for repairing the channels.
            5. Nice appearance and durability
            The enclosure is made of AL-plates and color steel sandwich plates, it is given the pre- treatment and plating treatment , besides, it also can be non-metallic enclosure made of a glass fiber and special cement and with the special technology so it has the obvious advantage like the strong plasticity of appearance, corrosion resistance, heat isolation and sound isolation etc. The surface coating is beautiful and durable, with high cohesion and soft color sense.

            High-side main circuit scheme

            圖片2

            Low-side circuit scheme

            圖片3

            Typical system scenario example reference

            圖片4

          1. Previous:
          2. Next:

          3. 福利吃瓜视频点击【23858.cc】久久久久精品国产亚洲AV无码欧美亚洲国产精品久久高清亚洲国产欧美目韩成人综合国产欧美日韩一区二区三区在线国产精品国产精品一区精品国产自在现偷99精品国产在热2019国产拍偷精品网国产精品视频全国免费观看,国产精品久久久久久AV下载红粉一级毛片在线看久久综合免费雪峰影视为您提供|国产精品久久久久久AV下载红粉一级毛片在线看久久综合免费欧美视频在线一区国产精品v欧美精品v日韩精品青青精品视频国产久久国产精品久久精品国产亚洲精品国产精品国产欧美精品一区二区三区国产精品第一页国产亚洲精品国产福利国产精品自拍国产精品视频在线观看亚洲国产精品一区二区久久国产精品国产三级国产专不,精品国产乱码久久久久久浪潮精品国产91乱码一区二区三区国产精品无码久久久久成人影院99在线无码精品秘入口国产精品一区二区三区狠狠做五月深爱婷婷综合亚洲麻豆AV无国产精品视频大陆精大陆国产国语精品2019精品国产品对白在线21年香蕉精品国产高清自在自线隔壁老王国产在线精品在线观看精品国产福利片,亚洲国产成人精品久久久999精品久久久国产亚州高清国产拍精品女人和拘做受全程看视频欧美一级黄色片亚洲国产成人久久综合碰碰动漫3d午夜一级毛片国产精品视频大陆精大陆国产国语精品2019精品国产品对白在线30年香蕉精品国产高清自在自线隔壁老王国产在线精品在线观看精品国产福利片,国产三级精品三级在专区精品国产自在现偷国产精品一区二区三区国产日韩精品欧美一区喷水亚洲精品国产精品国自产国产在线精品一区二区不卡日本α片无遮挡在线观看印度人又粗又长硬配种国产一区不卡老师脱了衣服让我爽了一夜视频白丝小舞被啪到娇喘不停久久久综合香蕉尹人综合网欧美高清XXXX极品粗大